Process Meter 9300 Series

  • Low-cost Alarm & Pump Controller
  • Alternates up to 4 pumps with time delay
  • NEMA 4X Front Face (optional enclosure)
  • 4-20 mA Analog Input & Output
  • Two-Line, 6 Digit Display
  • Power Supply 85-250 VAC or 12/24 VDC
  • 24 VDC Transmitter Power Supply
  • Horizontal Tank Volume Conversion
Categories: ,

Description

  • Low-cost Alarm & Pump Controller
  • Alternates up to 4 pumps with time delay
  • NEMA 4X Front Face (optional enclosure)
  • 4-20 mA Analog Input & Output
  • Two-Line, 6 Digit Display
  • Power Supply 85-250 VAC or 12/24 VDC
  • 24 VDC Transmitter Power Supply
  • Horizontal Tank Volume Conversion

Specs

Specifications
Display: Top 0.6″, Bottom 0.45″ Ht, red LED, 6 digits (-999999 to 999999), 8 Intensity Levels
Front Panel: NEMA 4X, IP65; panel gasket provided with four front panel buttons
Password: Restricts modification of programmed settings
Non-Volatile Memory: Settings stored for a minimum of 10 years
Power Options: 85-265 VAC, 50/60 Hz; 20 W max or 12-36 VDC; 6 W max
Required Fuse: UL Recognized, 5 A max, slow-blow
Isolated Transmitter: 5, 10 or 24 VDC selectable via jumper, 700Ω max
Operating Temperature: -40 to 150ºC
Storage Temperature: -40 to 185ºC
Connections: Removable terminal blocks accept 12-22 AWG. Note: RJ45 external I/O only
Panel: 1/8 DIN, high impact plastic, 94V-0, color; gray, weight = 9.5 oz (269 g)
Mounting Cut-out: 1/8 DIN panel cutout required 3.622″ x 1.772″ (92 x 45mm). Brackets included
Dimensions: 2.45″ x 4.68″ x 5.64″ (62mm x 119mm x 143mm), W x H x D
Inputs: Field selectable: 0-20 mA, 4-20 mA, 0-5 VDC, 1-5 VDC, 0-10 VDC
Accuracy: ±0.03% FS ±1 count, Linear, square root, exponent, horizontal tank volume, 32 pt DIY Table
Calibration Range: User programmable over entire range of meter, up to 5 decimal places
Relays: 0, 2 or 4 SPDT Form C, rated 3A @ 30VDC and 125/250 VAC
Relay Operation: Pump, Alteration Control, Automatic (non-latching), Latching, Sampling (based on time).
Time Delay: 0 to 999 seconds, on and off relay time delays, each relay is programmable separately
Fail-Safe: Programmable and Independent for each relay. 
Analog Output: 1 Isolated 4-20mA Output, 0.1% FS accuracy

Applications

Typically used as a remote display with our low-cost Bullet (Loop-powered ultrasonic level transmitter) or our Oyster (Submersible pressure transducer).

Advice & FAQ

1.  Yes, it has a built-in 24VDC power supply for loop-powered level or flow meters.
2.  Yes, it can display any units of measurement like ft, in, m, cm, mm.

Reviews

There are no reviews yet.

Be the first to review “Process Meter 9300 Series”

Your email address will not be published. Required fields are marked *